Modbus Register Definitions

This guide explains how to control a DFRobot N20 motor module using Modbus-RTU protocol, including changing the device address and restoring factory defaults. It covers hardware setup, wiring, and command sending. The key registers and function codes are detailed, with examples for driving the motor and modifying settings.

Register Definitions

Register Type Register Address Name R/W Data Range (16‑bit) Default Value Description
Input Register 0x0000 VID R 0x3343 0x3343 VID (Manufacturer ID for DFRobot)
Input Register 0x0001 PID R 0x0000~0xFFFF 0x04FD Product ID
Input Register 0x0002 Device Address R 0x0001~0x0020 0x0001 Reserved
Input Register 0x0003 Module Baud Rate R 0x0000~0xFFFF 0x0003 Reserved
Input Register 0x0004 Parity Bit(H) ‑ Stop Bit(L) R 0x0000~0xFFFF 0x0001 Reserved
Input Register 0x0005 VERSION R 0x0000~0xFFFF 0x1000 Firmware Version: 0x1000 stands for V1.0.0.0
Input Register 0x0006 Motor Status R 0x0000~0xFFFF 0x0000 Current motor status: 0=Stop, 100=Forward rotation, 200=Reverse rotation
Holding Register 0x0000 VID R/W 0x0000~0xFFFF 0xFFFF Reserved
Holding Register 0x0001 PID R/W 0x0000~0xFFFF 0xFFFF Reserved
Holding Register 0x0002 Device Address R/W 0x0001~0x0020 0x0001 Module slave address (1~247)
Holding Register 0x0003 Module Baud Rate R/W 0x0000~0x00FF 0x0003 Module baud rate:0x0001‑24000x0002‑48000x0003‑96000x0004‑144000x0005‑192000x0006‑384000x0007‑576000x0008‑115200Other values‑115200
Holding Register 0x0004 Parity Bit(H) ‑ Stop Bit(L) R/W 0x0000~0xFFFF 0x0001 Module parity bit (High byte) ‑ Stop bit (Low byte)Parity(H):0x00‑None0x01‑Even0x02‑OddOther‑NoneStop Bit(L):0x00‑0.5 Byte0x01‑1 Byte0x02‑1.5 Byte0x03‑2 ByteOther‑1 Byte
Holding Register 0x0005 VERSION R/W 0x0000~0xFFFF 0xFFFF Reserved
Holding Register 0x0006 Motor Status R/W 0x0000~0xFFFF 0x0000 Reserved
Holding Register 0x0007 Motor Speed R/W 0x0000~0xFFFF 0x0000 16‑bit signed motor speed, range ‑255~255.0=Stop, >0=Forward rotation, <0=Reverse rotation
Holding Register 0x0008 RESET R/W 0x0000~0x0001 0x0001 Restore factory defaults

Common Function Codes for Modbus-RTU:

Function Code Name Function
0x03 Read Multiple Registers Read integer, character, status word, floating-point (read N words) --- Read holding registers, byte operation
0x04 Read Input Registers Read integer, status word, floating-point (read N words) --- Read input registers, byte operation
0x06 Write Single Holding Register Write integer, character, status word, floating-point (write one word) --- Write holding register, byte operation
0x10 Write Multiple Holding Registers Write multiple holding registers --- Load specific binary values into a series of consecutive holding registers

Input and holding registers can be read and written using the above commands.

Example of Driving Motor Forward

Objective
Write to the holding registers of the N20 motor module via Modbus RTU protocol to control the motor to rotate forward at the specified speed.

Hardware Preparation

Wiring Diagram

DFR1277 Wiring Diagram

Connection Description:

Motor Pin: + Connect to Main Controller Pin: 5V
Motor Pin: - Connect to Main Controller Pin: GND
Motor Pin: R Connect to Main Controller Pin: TX
Motor Pin: T Connect to Main Controller Pin: RX

General Operation Steps

Hardware Connection: Connect the N20 motor module to the host (PC) via the RainbowLink USB protocol converter. The factory default RTU slave address is 0x0001.

Parameter Configuration: Set parameters in the serial debug tool (must match the factory default configuration of the motor module):

  • Baud rate: 9600 (default)
  • Data bits: 8
  • Stop bits: 1
  • Parity: None

Send Command: Enter the hexadecimal command below in the "Send Area" of the debug tool, check the "Send as Hex" option, then send.

Send Command & Parsing

Note: The register controlling motor speed is holding register 0x0007, a 16-bit signed integer. Positive values indicate forward rotation and negative values indicate reverse rotation, with a value range of -255 ~ 255. This example sets speed = 100 for motor forward rotation.

Field Name Hex Value Description
Device Address 01 MODBUS device address, default 0x0001
Function Code 06 Write Single Holding Register (fixed command)
Register Starting Address 00 07 Motor speed holding register address (0x0007)
Write Data 00 64 Set speed to 100, 16-bit signed positive number for forward rotation
CRC Check 39 E0 CRC16 check value of the command

Full Send Command: 01 06 00 07 00 64 39 E0

Response Data & Parsing

After receiving a valid write command, the motor module echoes the identical message frame as the response:

Field Name Hex Value Description
Device Address 01 Consistent with the device address in the send command
Function Code 06 Confirms execution of "Write Single Holding Register" operation
Register Starting Address 00 07 Address of the written register
Written Data 00 64 Actual written speed value
CRC Check 39 E0 CRC16 check value of the response frame

Full Response Data: 01 06 00 07 00 64 39 E0

Notes

  • To stop the motor, write 00 00 to holding register 0x0007. Full command: 01 06 00 07 00 00 38 0B.

  • If you have modified the module’s device address, baud rate, parity or stop bits, the serial debug tool parameters and the device address inside the command must be modified accordingly.

DFR1277-modbus result

Example of Modifying Device Address and Restoring Factory Defaults

Objective

Write to holding registers via the Modbus RTU protocol to change the device address of the N20 motor module from the default 0x01 to 0x02. After modifying the address, power-cycle the module for the new address to take effect. Then send the factory reset command to restore the module to factory default parameters (the device address will revert to 0x01).

Hardware Preparation

Wiring Diagram

DFR1277 Wiring Diagram

Connection Description:

Motor Pin: + Connect to Main Controller Pin: 5V
Motor Pin: - Connect to Main Controller Pin: GND
Motor Pin: R Connect to Main Controller Pin: TX
Motor Pin: T Connect to Main Controller Pin: RX

General Operation Steps

Hardware Connection: Connect the N20 motor module to the host (PC) via the RainbowLink USB protocol converter. The factory default RTU slave address is 0x0001.

Parameter Configuration: Set parameters in the serial debug tool (must match the factory default configuration of the motor module):

  • Baud rate: 9600 (default)
  • Data bits: 8
  • Stop bits: 1
  • Parity: None

Send Command: Enter the hexadecimal command below in the "Send Area" of the debug tool, check the "Send as Hex" option, then send.

Part 1: Modify Device Address (0x01 → 0x02)

Important Note: Writing to the address register only saves the configuration. You must power-cycle the module for the new device address to take effect. The old address 0x01 is still used for communication before reboot.

Send Command & Parsing

Field Name Hex Value Description
Device Address 01 MODBUS device address, default 0x0001 before modification
Function Code 06 Write Single Holding Register (fixed command)
Register Starting Address 00 02 Device address holding register address (0x0002)
Write Data 00 02 Set the new module device address to 0x0002
CRC Check A9 CB CRC16 check value of the command

Full Send Command: 01 06 00 02 00 02 A9 CB

Response Data & Parsing

After receiving a valid write command, the motor module echoes the identical message frame as the response:

Field Name Hex Value Description
Device Address 01 Consistent with the old device address in the send command
Function Code 06 Confirms execution of "Write Single Holding Register" operation
Register Starting Address 00 02 Address of the written register
Written Data 00 02 New device address value to be written
CRC Check A9 CB CRC16 check value of the response frame

Full Response Data: 01 06 00 02 00 02 A9 CB

Interpretation of Address Modification Result

Receiving the response frame means the new address configuration has been saved inside the module, but the new address is not active yet.

  • Power off the module and re-power it to reboot.

  • After reboot, the new address 0x02 takes effect. The first byte of all subsequent communication commands must be changed to 02 to communicate with the module.

Address verification command after reboot (new address 0x02, read input register 0x0002): 02 04 00 02 00 01 90 39 The module follows the standard Modbus-RTU big-endian mode; no byte swap is required. Actual returned frame: 02 04 02 00 02 7C F1. The data bytes 00 02 represent the read device address 0x0002, confirming the address modification is completed.

Part 2: Restore Factory Defaults (Current address 0x02, revert to 0x01 after reset)

Register Definition: Holding register 0x0008 RESET. Write 0x0001 to trigger factory reset. A power cycle is also required for factory reset to load and apply default settings.

Send Command & Parsing

Field Name Hex Value Description
Device Address 02 Current MODBUS device address of the module, 0x0002 after reboot
Function Code 06 Write Single Holding Register (fixed command)
Register Starting Address 00 08 Factory reset register address (0x0008)
Write Data 00 01 Trigger factory reset
CRC Check C9 FB CRC16 check value of the command

Full Send Command: 02 06 00 08 00 01 C9 FB

Response Data & Parsing

After the motor module receives and successfully executes the factory reset command, it returns the original sent frame:

Field Name Hex Value Description
Device Address 02 Device address before reset execution
Function Code 06 Confirms execution of "Write Single Holding Register" operation
Register Starting Address 00 08 Address of the written register
Written Data 00 01 Reset trigger value
CRC Check C9 FB CRC16 check value of the response frame

Full Response Data: 02 06 00 08 00 01 C9 FB

Interpretation of Factory Reset Result

Once the module returns the response frame, the factory reset configuration is saved. Power-cycle the module to load factory parameters. After reboot, all parameters restore to factory defaults: device address reverts to 0x0001, baud rate 9600, default parity and stop bit settings, and motor speed cleared to stop.

Verification command after reboot (address reverts to 0x01): 01 04 00 02 00 01 90 0A. Parse returned data bytes in standard big-endian order. Reading 0x0001 confirms factory reset takes effect.

Notes

  • After successful writing for device address modification, the module must be power-cycled for the new address to take effect. Factory reset also requires a power cycle after writing, the address will switch back to 0x01, and the first byte of the message must be modified accordingly.

  • Valid device address range: 1–247. Do not write 0, otherwise module communication will be abnormal.

  • Factory reset clears user configurations: communication baud rate, parity, stop bits and running speed all revert to factory defaults, which will be loaded after power cycle.