Communication Protocol Description

The sensor adopts RS485 communication interface and supports standard Modbus-RTU protocol. Below is the register description:

Register Address Number Name Read/Write Data Range Default Value Data Description
0x00 1 Module PID Register R 0x0000-0xFFFF 0x0001 Product check (Detect module type)
0x01 1 Module VID Register R 0x0000-0xFFFF 0x0010 Version check (0x0010 represents V0.0.1.0)
0x02 1 Module Address Register R/W 0x0001-0x00F7 0x000B When the sensor address is unknown, write to the register through the broadcast address 0x00, at this time, the sensor will not have data output
0x03 1 Serial parameter control register 1 R/W 0x0000-0xFFFF 0x0005 Module Baudrate:
0x0001---2400
0x0003---9600
0x0004---14400
0x0005---19200
0x0006---38400
0x0007---57600
0x0008---115200
Other----115200
0x04 1 Serial parameter control register 2 R/W 0x0000-0xFFFF 0x0001 Module check bit H:  Stop bit L:
0x00---None     0x00---0.5byte
0x01---Even       0x01---1byte
0x02---Odd      0x02---1.5byte
other---none     0x03---2byte
            Other---1byte
0x05 1 Distance register R 0x0000-0xFFFF 0x0000 The distance value LSB measured by the module represents 1cm
0x06 1 Onboard temperature data register R 0x0000-0xFFFF 0x0000 The temperature value measured by the onboard temperature sensor represents 0.1℃ (with unit symbol)
0x07 1 External temperature compensation data register R/W 0x0000-0xFFFF 0x0000 LSB write ambient temperature data to this register for external temperature compensation represents 0.1℃ (with unit symbol)
0x08 1 Control register R/W 0x0000-0xFFFF 0x0004 bit 1-0
00-use onboard temperature compensation function
01-use external temperature compensation function(Users need to write temperature data to external temperature compensation data register)
1x-Not use temperature compensation function
bit 2:
0-auto detection
1-passive detection
bit 3:
In passive detection mode, write 1 to this bit, then it will measure distance once. The distance value can be read from distance register 300ms later. This bit is disabled in passive detection mode.

Principle

Normally, the detection area of an ultrasonic sensor is irregular and hard to define due to its physical characteristics. In actual use, we found that the detection area and sensitivity of this sensor may be larger than other ultrasonic sensors. Therefore, when the sensor is used in a narrow space, a non-target object may be detected.

We used two kinds of reference target obstacles to repeatedly test many sample products. The reference detection area of the corresponding target is as follows:

  • Detection area for 7.5cm PVC pipe

PVC

  • Detection area for 100x30cm plane plate

Plane plate